Specification
|
GRV-ITR-12
|
Input Ranges (Ohms)
|
400 k, 200 k, 100 k, 50 k, 40 k, 20 k, 10 k, 5 k, 4 k, 2 k, 1 k, 500 and Autorange
|
Accuracy, normal mode (Ohms @ Range)
|
0.1%; specific values for indicated range:
400@400 k, 200@200 k, 100@100 k, 50@50 k, 40@40 k, 20@20 k, 10@10 k, 5@5 k, 4@4 k, 2@2 k, 1@1 k, 0.5@500
|
Accuracy, fast ADC mode (Ohms @ Range)
|
0.5%; specific values for indicated range:
2000@400 k, 1000@200 k, 500@100 k, 250@50 k, 200@40 k, 100@20 k, 50@10 k, 25@5 k, 20@4 k, 10@2 k, 5@1 k, 2.5@500
|
Excitation Current (Range & Load Watts Dissipated)
|
>7.9 µA (400 K & 25 µW), (200 K & 12.4 µW), (100 K & 6.2 µW), (50 K & 3.1 µW),
>84.7 µA (40 K & 287 µW), (20 K & 144 µW), (10 K & 72 µW), (5 K & 36 µW),
>169.2 µA (4 K & 115 µW), (2 K & 57 µW), (1 K & 29 µW), (500 & 14 µW)
|
Analog Data Filtering
|
-3 dB @ 2.4 Hz
-25 dB @ 60 Hz
|
Software Data Filtering:
|
-
1 to 32 readings
-
1 to 4096
|
Data Refresh Time (normal mode)
|
900 ms
|
Data Refresh Time (fast ADC mode)
|
450 ms
|
Step Input Response Time (normal mode)
|
900 ms x SMA value (for example, 28.8 s @ 32 SMA, Default SMA = 4)
|
Step Input Response Time (fast ADC mode)
|
450 ms x SMA value (for example, 14.4 s @ 32 SMA, Default SMA = 4)
|
Quaility Indications
|
out of range
|
Isolation (field-to-logic)
|
300 V working, 1500 V transient (1 minute)
|
Isolation (channel-to-channel)
|
300 V between channel group 0–5 & channel group 6–11. None within a group.
|
Number of Channels
|
12
|
Chassis Power Consumption
|
1.3 W
|
Minimum groov EPIC Firmware Version
|
1.3.0
|
Minimum PAC Project Version
|
10.2000
|
Minimum Library Package for CODESYS Version
|
1.0.0.0
|
Wire Size
|
28–14 AWG
|
Wire Strip Length
|
0.315–0.354 inches (8–9 mm)
|
Torque, connector screw
|
2.5 in-lb (0.28 N-m)
|
Torque, hold-down screw
|
3.5 in-lb (0.4 N-m)
|
Temperature (operating)
|
-20 °C to +70 °C
|
Temperature (storage)
|
-40 °C to +85 °C
|
Relative Humidity (non-condensing)
|
5–95%
|
MTBF (minimum, 25 °C)
|
1.2 Mhrs
|
Agency Approvals
|
UL/cUL (Class 1, Div 2)a; CE: ATEX (Category 3, Zone 2) and RoHS; DFARS; CB Scheme; UKCA
|
Warranty
|
Lifetime
|