G4 I/O family
The G4OAC5A is a digital AC output module with an output voltage range of 24-280 VAC, requiring a typical logic voltage of 5 VDC. It is compatible with Opto 22 brains and Raspberry Pi.
This AC output module is equivalent to a single-pole, single-throw, normally open contact (Form A, SPST-NO). It includes a 4 amp fast-blow fuse.
Opto 22’s G4 AC output modules are used to control or switch AC loads. Each module provides up to 4000 volts of optical isolation (transient) between field outputs and the control side of the circuit, and each features zero voltage turn-on and zero current turn-off.
Typical applications for AC output modules include switching loads such as AC relays, solenoids, motor starters, heaters, lamps, and indicators.
Compatible with Raspberry Pi. The G4OAC5A can be used with the Digital I/O Carrier Board for Raspberry Pi® (part number OPTO-P1-40P) to monitor and control industrial devices with your Raspberry Pi.
|
Units
|
G4OAC5*
|
G4OAC5A*
|
G4OAC5A5*
|
G4OAC5MA*
|
G4OAC5AMA*
|
Nominal line voltage
|
VAC
|
120
|
120/240
|
120/240
|
120
|
120/240
|
Output voltage range
|
VAC
|
12–140
|
24–280
|
24–280
|
12–140
|
24–280
|
Key feature
|
—
|
—
|
—
|
Normally closed
|
Diagnostic
switch
|
Diagnostic
switch
|
Current rating:
At 45 °C ambient
At 70 °C ambient
|
A
A
|
3
2
|
3
2
|
3
2
|
3
2
|
3
2
|
UL Motor Load Rating
|
A
|
1.5
|
1.5
|
1.5
|
1.5
|
1.5
|
Isolation input-to-
output (transient):
1 ms
1 minute
|
volts
|
4000
1500
|
4000
1500
|
4000
1500
|
4000
1500
|
4000
1500
|
Off-state leakage at
nominal voltage (60 Hz)
|
mARMS
|
5
|
1.25/2.5
|
1.25/2.5
|
5
|
1.25/2.5
|
Nominal logic voltage
|
VDC
|
5
|
5
|
5
|
5
|
5
|
Logic voltage range
|
VDC
|
4–8
|
4–8
|
4–8
|
4–8
|
4–8
|
Logic pickup voltage
|
VDC
|
4
|
4
|
4
|
4
|
4
|
Logic dropout voltage
|
VDC
|
1
|
1
|
1
|
1
|
1
|
Logic input current at
nominal logic voltage
|
mA
|
12
|
12
|
12
|
12
|
12
|
Control resistance
(Rc in schematic)
|
ohms
|
220
|
220
|
220
|
220
|
220
|
One-cycle surge
|
A peak
|
80
|
80
|
80
|
80
|
80
|
Turn-on time @ 60 Hz
|
milliseconds
|
≤8.3***
|
≤8.3***
|
≤8.3***
|
≤8.3***
|
≤8.3***
|
Turn-off time @ 60 Hz
|
milliseconds
|
≤8.3****
|
≤8.3****
|
≤8.3****
|
≤8.3****
|
≤8.3****
|
Peak repetitive voltage
|
VAC
|
500
|
500
|
500
|
500
|
500
|
Minimum load current
|
mA
|
20
|
20
|
20
|
20
|
20
|
Output voltage drop
maximum peak
|
V
|
1.6
|
1.6
|
1.6
|
1.6
|
1.6
|
Operating frequency
|
Hz
|
25–65
|
25–65
|
25–65
|
25–65
|
25–65
|
dV/dT-off-state
|
V/micro-seconds
|
200
|
200
|
200
|
200
|
200
|
dV/dT-commutating
|
--
|
snubbed for
0.5 power
factor load
|
snubbed for
0.5 power
factor load
|
snubbed for
0.5 power
factor load
|
snubbed for
0.5 power
factor load
|
snubbed for
0.5 power
factor load
|
Temperature
Operating:
Storage:
|
°C
°C
|
-30 to +70
-30 to +85
|
-30 to +70
-30 to +85
|
-30 to +70
-30 to +85
|
-30 to +70
-30 to +85
|
-30 to +70
-30 to +85
|
Agency Approvals |
|
UL, CE, CSA; UKCA |
UL, CE, CSA; UKCA |
CE, CSA; UKCA
|
UL, CE, CSA; UKCA |
UL, CE, CSA, RoHS; UKCA |
**** One-half cycle maximum. Module turns on at the zero volt crossing of the AC sine wave.
**** One-half cycle maximum. Module turns off at the zero current crossing of the AC sine wave.
|
Opto 22’s G4 AC output modules are used to control or switch AC loads. This document includes descriptions, specifications, and wiring and dimensional diagrams for Opto 22’s G4 AC output modules:
The G4 Digital I/O Data Book provides complete details on every G4 digital I/O product component, including adapter cards, I/O modules, and mounting racks.
This document is the Manufacturer's Declaration of Conformity for the products listed herein, in accordance with the rules, regulations and standards of the United Kingdom. The models cited have been tested to the essential requirements listed in the Standards section, and fully comply with the legislation as listed in UK Legislation section.
This document is the Manufacturer's Declaration of Conformity for the products listed herein, in accordance with European, international, and/or national standards and regulations.
This document is a statement of compliance with the EU Directive 2015/863/EU, Restriction of Hazardous Substances (RoHS 3). This document lists Opto 22 products that comply with the substance restrictions of the RoHS 3 directive.
Wiring diagrams for G4 modules and racks
This document lists all Opto 22 part numbers that have the Canadian Standards Association (CSA) approval.
This document lists all Opto 22 part numbers that have the Underwriters Laboratory (UL) approval.
This document is the Manufacturer's Declaration for the listed products as mentioned in the attachment - to which this confirmation refers - that they are in accordance with the mentioned European, international and/or national standards and regulations.
This document is the Manufacturer's Declaration for the listed products as mentioned in the attachment - to which this confirmation refers - that they are in accordance with the mentioned European, international and/or national standards and regulations.
No downloads are available for this product.
No videos or demos are available for this product.